CPSCJanuary 28, 2014

System Sensor Reflected Beam Smoke Detectors recall: Failure to Alert Consumers in a Fire

System Sensor Recalls Reflected Beam Smoke Detectors Due To Failure to Alert Consumers in a Fire (Recall Alert)

Why was System Sensor Reflected Beam Smoke Detectors recalled?

When used with certain power supplies, the reflected beam smoke detectors can fail to send a signal to the fire alarm control panel that sounds the alarm and fail to alert occupants of a fire.

What should I do if I have this product?

Owners with the affected smoke detectors powered by a power supply that is not on the company's acceptable list available online, should contact System Sensor to receive free replacement smoke detectors. System Sensor and its distributors are contacting purchasers directly. Contact: System Sensor at (800) 736-7672 from 7:30 a.m. through 5 p.m. CT Monday through Friday, or online at www.systemsensor.com and click on Resources, then Product Info Library/Technical Field Bulletins, then Safety Bulletins for more information and a list of acceptable power supplies.

What to do with a recalled product: refunds, receipts, safe disposal and how to report a problem.

Is my product affected?

Compare the item in your hand with every identifier below from the official CPSC record. Only products that match the listed product and identifiers are part of this recall.

Product
System Sensor reflected beam smoke detectors
Company
System Sensor, of St. Charles, Ill.
Quantity
About 610
Sold at
Alarm system, security equipment and electrical equipment contractors and dealers for use in commercial building fire alarm systems from November 2012 through May 2013 for about $800.
Recall date
January 28, 2014
Incidents / injuries
None reported
Agency
CPSC

Product description

This recall involves System Sensor's reflected beam smoke detectors with model number BEAM1224S and date codes 2111 through 3053. The YMMW format date codes stand for (2111) 2012-November-1st week of Nov. through (3053) 2013-May-3rd week of May. The detectors are ivory and black and measure 10 inches high by 7½ inches wide. The model number and date code are printed on a label on the back of the detector's cover and on the product's packaging. The reflected beam smoke detectors were used primarily in commercial buildings as part of the fire alarm system. Detectors used with acceptable power supplies, as listed on the company website, do not need to be replaced.