CPSCMarch 18, 2014

Schneider Electric Square D-Brand F and K Frame Circuit recall: Fire Hazard

Schneider Electric Recalls Square D-Brand F and K Frame Circuit Breakers Due to Fire Hazard

Why was Schneider Electric Square D-Brand F and K Frame Circuit recalled?

The circuit breaker can fail to trip when an overload occurs, posing the risk of fire, burn and electric shock.

What should I do if I have this product?

Consumers should immediately check to see if they have the recalled circuit breakers. Consumers with uninstalled products will receive a replacement. Installed products will be replaced at no charge to the customer with an allowance of up to $300 per site to cover labor costs. Contact: Schneider Electric USA at (800) 634-8730 anytime. Consumers can also visit the firm's website at www.schneider-electric.us and click on "customer notification" under the popular links category for more information.

What to do with a recalled product: refunds, receipts, safe disposal and how to report a problem.

Is my product affected?

Compare the item in your hand with every identifier below from the official CPSC record. Only products that match the listed product and identifiers are part of this recall.

Product
Square D branded, molded case F and K frame circuit breakers
Company
Schneider Electric USA Inc., of Palatine, Ill.
Quantity
About 28,400
Sold at
Authorized Schneider Electric distributors nationwide such as Border States Electric Supply, Crescent Electric Supply Co., Dealers Electric Supply Co., Graybar Electric Co., Rexel, W.W. Grainger from May 2013 to June 2013 for between $200 and $9,260.
Recall date
March 18, 2014
Incidents / injuries
None reported.
Agency
CPSC

Product description

This recall involves Square D brand models FA, FH, FI and FY one-, two- and three-pole circuit breakers rated 15 to 100 amps, and model KI two- and three-pole circuit breakers rated 110 to 250 amps. The F model breakers were manufactured May 8, 2013 through June 10, 2013 and have date codes 13193 through 13241. The K models were manufactured May 2, 2013 through June 21, 2013 and have date codes 13184 through 13255. The date codes are YYWWD format (example: 13184 = year 2013, week 18, day of the work week 4/ Thursday). The circuit breakers have a yellow label with the words "Square D" or the Square D logo. Model information can be found on the faceplate.

Open official CPSC notice Latest recalls