CPSCFebruary 18, 2010

GE Infrastructure Sensing Commercial CO2 and Temperature recall: Fire Hazard

GE Infrastructure Sensing Recalls Commercial CO2 and Temperature Sensors Due to Fire Hazard

Why was GE Infrastructure Sensing Commercial CO2 and Temperature recalled?

The CO2 and temperature sensors can overheat, posing a fire hazard.

What should I do if I have this product?

Building owners should immediately contact GE Infrastructure Sensing for instructions on how to determine if a sensor is included in this recall and if it can be used while awaiting a replacement sensor. Only authorized maintenance personnel should follow these instructions. Building owners with recalled sensors will receive a free replacement sensor. Contact: For additional information, contact GE Infrastructure Sensing toll-free at (877) 243-5086 between 8 a.m. and 5:00 p.m. ET or visit the company's website at www.gesensing.com

What to do with a recalled product: refunds, receipts, safe disposal and how to report a problem.

Is my product affected?

Compare the item in your hand with every identifier below from the official CPSC record. Only products that match the listed product and identifiers are part of this recall.

Product
GE Telaire Airestat and Carrier Single Beam Carbon Dioxide (CO2) and Temperature Sensors
Company
GE Infrastructure Sensing Inc., of Billerica, Mass.
Quantity
About 9,400 units
Sold at
Carrier, Automated Components Incorporated (ACI), Devices Inc., Direct Digital Controls, Trane, Alps Control Inc., ATS Control Management Inc. and KMC Controls between November 2000 and March 2005 for between $150 and $200. The recalled sensor was distributed for use in commercial buildings.
Recall date
February 18, 2010
Incidents / injuries
GE has received three reports in which a cracked capacitor caused the product to overheat and smoke. No injuries have been reported.
Agency
CPSC

Product description

This recall involves GE Telaire Airestat CO2 and temperature sensors with model numbers T8010, T8010-C, T8011, T8011-C, T5010, T5010-C, T5011 and T5011-C and Carrier Single Beam CO2 and temperature sensors with model numbers 33ZCT55CO2 and 33ZCT56CO2. The sensors are sold for commercial use and are wall-mounted. The sensors have a Telaire, Carrier, or no logo in front of the unit. The model number is not found on the sensor. Determining if a sensor is included in this recall requires inspection of the internal components of the unit.