CPSC, Viessmann Manufacturing Company recall

CPSC, Viessmann Manufacturing Company (U.S.) Inc., Announce Recall of SR-RN-2 and SR-RN2R Boiler Control

Why was CPSC, Viessmann Manufacturing Company recalled?

The controls have an electronic relay that may fail in a manner that will allow the burner to operate and by-pass the interlock with the flue damper. The interlock assures proper operation of the damper for removal of combustion gases. If the interlock fails, excess carbon monoxide emissions may occur.

What should I do if I have this product?

Consumers who have one of these boilers should contact their local distributor or Ms. Ulli Hiltz, the Viessmann Manufacturing Company contact. Viessmann Manufacturing Company will install a wiring module in suspect boilers which will put a redundant switch in series with the switch that may erroneously close and by-pass the safety interlock with flue damper. Viessmann Manufacturing Company has contacted distributors and wholesalers and made arrangements for them to contact customers and make arrangements to retrofit the Atola-RN Boilers with SR-RN2 or SR-RN2R Controls. Contact: Ms. Ulli Hiltz, the Viessmann Manufacturing Company contact, can be reached at 888-843-2772 between 8:30am and 5:00 pm ET Monday through Friday.

What to do with a recalled product: refunds, receipts, safe disposal and how to report a problem.

Is my product affected?

Compare the item in your hand with every identifier below from the official CPSC record. Only products that match the listed product and identifiers are part of this recall.

Product
SR-RN-2 and SR-RN2R Boiler Control
Company
Viessmann Manufacturing Company (U.S.), of Warwick, R.I.
Quantity
190
Sold at
The boilers were sold nationwide by wholesalers and distributors.
Recall date
March 13, 2002
Incidents / injuries
No injuries have been reported.
Agency
CPSC

Product description

The recalled units, which are installed in Atola-RN Boilers, were manufactured between December 1998 and December 2001. This is the entire production of these controls. (The controls do not have a date code that can be seen by consumers.)